6. WIRING
6.1 Power Supply Wiring
Connect the power terminal on the GOT rear face with the 24VDC terminal of the
external power.
Use 0.75mm
2
or more cables so as not to produce voltage drops.
Use solderless terminals for M3 screws, and be sure to tighten the screws with a
tightening torque of 0.5 to 0.8N
m.
The independent grounding is basically required.
Ground the GOT with a ground resistance of 100 or less.
If the independent grounding is impossible, carry out the shared grounding as
shown in fig.2) below.
Use the cable of 2mm
2
or more for grounding.
Set the grounding point closer to the GOT to make the grounding cable short as
possible.
1) Recommended terminal shape
7. MAINTENANCE AND INSPECTION
The GOT does not include consumable components that will cause the shorten life.
However, note that battery life is 5 years and LCD life is 50,000 hours. The life of
backlight in GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ, GT1155-QSBDA
is 75,000 hours and that in GT1150-QLBDQ, GT1150-QLBDA is 54,000 hours.
It is recommended to replace the battery periodically. (For the replacement of the
liquid crystal screen and backlight, please consult your nearest sales office or FA
Center.)
7.1 Daily Inspection
Daily inspection items
Refer to the following for the model names of the protection sheet or the replacement
procedure.
GT11 User’s Manual
7.2 Periodic Inspection
Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved
or modified or the wiring changed.
7.3 Battery Replacement
The battery backs up clock data, alarm history and recipe data.
Screen data is stored in the flash memory and data is retained even if the battery is
dead.
Battery model name
GT11 is shipped with the following battery.
Applicable solderless terminal RAV 1.25-3, V2-N3A and FV2-N3A
Programmable controller
connection cable
Connection cable for
personal computer or
bar code reader
24VDC
power
supply
Grounding
GOT GOT GOT
Other
device
Other
device
Other
device
Grounding
Grounding
(1) Independent ground
...... Best condition
(2) Shared grounding
...... Good condition
(3) Common grounding
...... Not allowed
Terminal
screw
Solderless
terminal
Terminal
screw
6.2mm
or less
3.2
3.2
6.2mm
or less
When wiring one cable to
one terminal
When wiring two cables to
one terminal
Solderless
terminal
No. Inspection Item
Inspection
Method
Criterion Action
1 GOT mounting status
Check for
loose mounting
screws.
Securely
mounted
Retighten screws
within the
specified torque
range
2
Connection status
Loose terminal
screws
Retighten
screws with
screwdriver
Not loose
Retighten
terminal screws
Proximate
solderless
terminals
Visual check
Proper
intervals
Correct
Loose connectors Visual check Not loose
Retighten
connector fixing
screws
3
Usage status
Dirt on protection
sheet
Visual check
Not
outstanding
Replace with new
one
Foreign material
attachment
Visual check
No foreign
matter sticking
Remove clean
No. Inspection Item
Inspection
Method
Criterion Action
1
Surrounding
environment
Ambient
temperature
Make
measurement
with
thermometer
or hygrometer
Measure
corrosive gas
Display
section
0 to
50
For use in
control panel,
temperature
inside control
panel is ambient
temperature
Other
portions
0 to
55
Ambient
humidity
10 to 90%RH
Atmosphere
No corrosive
gas
2
Power supply voltage
check
24VDC
Measure
voltage across
terminals.
20.4 to
26.4VDC
Change supply
power
3
Connection
status
Loose
terminal
screws
Retighten
screws with
screwdriver
Not loose
Retighten
terminal screws
Proximate
solderless
terminals
Visual check
Proper
intervals
Correct
Loose
connectors
Visual check Not loose
Retighten
connector fixing
screws
Product name Model name
Battery GT11-50BAT
Battery replacement procedure
1) Turn the GOT power off.
2) Open the back cover of the GOT.
3) Remove the old battery from the
holder.
4) Disconnect the old battery connector
and insert the new battery connector
within 30s.
(Clock data, alarm history, and
recipe data is retained by the GOT
condenser for 30 seconds.)
5) Insert the new battery into the holder
and close the back cover.
How to confirm production year and
month
The production year and month of the battery built in the purchased GOT can be
confirmed by the production No. (serial No.) marked on the GOT main unit.
Battery life
Approximate battery life:
5 years (ambient temperature: 25 ) [Guaranteed for 1 year]
Battery replacement: In 4 to 5 years
Approximate life is 5 years, but life may be shorter depending on the ambient
temperature, therefore, note that the battery must be replaced in 4 to 5 years.
Make sure to purchase a new battery as needed as it self-discharges.
Battery status can be confirmed on a GOT utility screen.
For details of battery status or how to output alarm, refer to the following:
GT11 User’s Manual
Back cover
Holder
Connector
Back cover
Holder
Connector
Day (example: 1st) 1 to 31: 1st to 31s
t
Year (example: 2007)
last digit
Month (example: Jun.). 1 to 9: Jan. to Sep.,
X: Oct., Y: Nov., Z: Dec.
MODEL
GRAPHIC OPERATION TERMINAL
SERIAL
GT1155-QTBDQ
00007201
DP00001-A
IN 24VDC
POWER MAX 00W
MITSUBISHI ELECTRIC
MADE IN JAPAN
Warranty
Mitsubishi will not be held liable for damage caused by factors found
not to be the cause of Mitsubishi; machine damage or lost profits
caused by faults in the Mitsubishi products; damage, secondary
damage, accident compensation caused by special factors
unpredictable by Mitsubishi; damages to products other than Mitsubishi
products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for
general industries, and has not been designed or manufactured to
be incorporated in a device or system used in purposes related to
human life.
Before using the product for special purposes such as nuclear
power, electric power, aerospace, medicine or passenger movement
vehicles, consult with Mitsubishi.
This product has been manufactured under strict quality control.
However, when installing the product where major accidents or
losses could occur if the product fails, install appropriate backup or
failsafe functions in the system.
Country/Region Sales office/Tel
U.S.A Mitsubishi Electric Automation Inc.
500 Corporate Woods Parkway Vernon Hills, IL 60061, U.S.A.
Tel : +1-847-478-2100
Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda.
Rua Correia Dias, 184, Edificio Paraiso Trade Center-8 andar
Paraiso, Sao Paulo, SP Brazil
Tel : +55-11-5908-8331
Germany Mitsubishi Electric Europe B.V. German Branch
Gothaer Strasse 8 D-40880 Ratingen, GERMANY
Tel : +49-2102-486-0
U.K Mitsubishi Electric Europe B.V. UK Branch
Travellers Lane, Hatfield, Hertfordshire., AL10 8XB, U.K.
Tel : +44-1707-276100
Italy Mitsubishi Electric Europe B.V. Italian Branch
Centro Dir. Colleoni, Pal. Perseo-Ingr.2
Via Paracelso 12, I-20041 Agrate Brianza., Milano, Italy
Tel : +39-039-60531
Spain Mitsubishi Electric Europe B.V. Spanish Branch
Carretera de Rubi 76-80,
E-08190 Sant Cugat del Valles, Barcelona, Spain
Tel : +34-93-565-3131
France Mitsubishi Electric Europe B.V. French Branch
25, Boulevard des Bouvets, F-92741 Nanterre Cedex, France
TEL: +33-1-5568-5568
South Africa Circuit Breaker Industries Ltd.
Private Bag 2016, ZA-1600 Isando, South Africa
Tel : +27-11-928-2000
Hong Kong Mitsubishi Electric Automation (Hong Kong) Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, Hong Kong
Tel : +852-2887-8870
China Mitsubishi Electric Automation (China) Ltd.
4/F Zhi Fu Plazz, No.80 Xin Chang Road,
Shanghai 200003, China
Tel : +86-21-6120-0808
Taiwan Setsuyo Enterprise Co., Ltd.
6F No.105 Wu-Kung 3rd.Rd, Wu-Ku Hsiang,
Taipei Hsine, Taiwan
Tel : +886-2-2299-2499
Korea Mitsubishi Electric Automation Korea Co., Ltd.
1480-6, Gayang-dong, Gangseo-ku Seoul
157-200, Korea
Tel : +82-2-3660-9552
Singapore Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building, Singapore 159943
Tel : +65-6470-2460
Thailand Mitsubishi Electric Automation (Thailand) Co., Ltd.
Bang-Chan Industrial Estate No.111 Moo 4, Serithai Rd,
T.Kannayao, A.Kannayao, Bangkok 10230 Thailand
Tel : +66-2-517-1326
Indonesia P.T. Autoteknindo Sumber Makmur
Muara Karang Selatan, Block A/Utara
No.1 Kav. No.11 Kawasan Industri Pergudangan
Jakarta - Utara 14440, P.O.Box 5045 Jakarta, 11050 Indonesia
Tel : +62-21-6630833
India Messung Systems Pvt, Ltd.
Electronic Sadan NO:III Unit No15, M.I.D.C Bhosari,
Pune-411026, India
Tel : +91-20-2712-3130
A
ustralia Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan, May 2011.
IB-0800385ENG-F-2/2
Zobrazit stránku 2
1 2 3

Komentáře k této Příručce

Žádné komentáře