3.3 Built-in Interface Specifications
3.4 Power Supply Specifications
*1 The GOT continues to operate even upon 5ms or shorter instantaneous power failure.
The GOT stops operating if there is extended power failure or voltage drop, while it automatically resumes operation as soon as the power is restored.
*2 A surge absorber is connected between the power supply and earth terminal so that the GOT does not malfunction due to applied lightning surge noise.
Values without a surge absorber are described for the dielectric withstand voltage and the insulation resistance.
3.5 External Dimensions
Item
Specifications
GT1155-QTBDQ
GT1155-QSBDQ
GT1150-QLBDQ
GT1155-QTBDA
GT1155-QSBDA
GT1150-QLBDA
Built-in
interface
BUS
Bus interface for connecting to the QCPU (Q mode) and motion
controller CPU (Q series) 1ch
Application : For communicating with a programmable controller
-
-
Bus interface for connecting to the QnACPU, ACPU, and motion
controller CPU (A series) 1ch
Application : For communicating with a programmable controller
RS-232
Conforming to serial RS232 standard, 1ch
Transmission speed: 115,200/57,600/38,400/19,200/9,600/4,800bps
Connector shape : D-sub 9-pin (Male)
Application : Bar code reader connection, Personal computer communication
(Project data upload/download, OS installation, transparent function)
USB
Conforming to serial USB (Full Speed 12Mbps), device, 1ch
Application: Personal computer communication (Project data upload/download, OS installation, transparent function)
CF card
Conforming to PCMCIA, compact flash slot, 1ch
Connector shape : Dedicated for TYPE I
Application : Data transfer, data storage
Item
Specifications
GT1155-QTBDQ
GT1155-QTBDA
GT1155-QSBDQ
GT1155-QSBDA
GT1150-QLBDQ
GT1150-QLBDA
Input power supply voltage 24VDC (+10% -15%), ripple voltage 200mV or less
Fuse (built-in, not exchangeable) 1.0A
Power consumption 11.16W (465mA/24VDC) or less 9.72W (405mA/24VDC) or less 7.92W (330mA/24VDC) or less
At backlight off 5.04W (210mA/24VDC) or less
Inrush current 26A or less (26.4V) 4ms
Permissible instantaneous power
failure time
*1
Within 10ms
Noise immunity Noise voltage: 500Vp-p, Noise width: 1s (by noise simulator of 25to 60Hz noise frequency)
Dielectric withstand voltage
*2
500VAC for 1 minute (across power supply terminals and earth)
Insulation resistance
*2
10M or larger by a 500VDC insulation resistance tester (across power supply terminals and earth)
Applicable wire size
0.75 to 2[mm
2
]
Applicable solderless terminal Solderless terminal for M3 screw RAV1.25-3, V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5 to 0.8[N
m]
167 (6.58)
28.5
(1.13)
21 (0.83)
135 (5.32)
62 (2.44)
6 (0.24)
48 (1.89)
65 (2.56)
10
(0.40)
120
(4.73)
10
(0.40)
110 (4.33)
#4-40UNC
(Inch screw
type)
Panel thickness:
5mm(0.2") or less
152 (5.99)
28.5
(1.13)
110 (4.33)
167 (6.58)
28.5
(1.13)
21 (0.83)
135 (5.32)
62 (2.44)
6 (0.24)
48 (1.89)
65 (2.56)
10
(0.40)
120
(4.73)
10
(0.40)
110 (4.33)
M2
(Metric screw
type)
#4-40UNC
(Inch screw type)
Panel thickness:
5mm(0.2") or less
Unit: mm (inch)
152 (5.99)
28.5
(1.13)
110 (4.33)
4
(0.16)
5
(0.20)
GT1155-QTBDA, GT1155-QSBDA, GT1150-QLBDAGT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ
4
(0.16)
5
(0.20)
4. EMC AND LOW VOLTAGE DIRECTIVE
For the products sold in European countries, the conformance to the EMC Directive,
which is one of the European Directives, has been a legal obligation since 1996.
Also, conformance to the Low Voltage Directive, another European DIrectives, has
been a legal obligation since 1997.
Manufacturers who recognize their products must conform to the EMC and Low
Voltage Directive are required to declare that their products conform to these
Directives and put a "CE mark" on their products.
Authorized representative in Europe
Authorized representative in Europe is shown below
Name :Mitsubishi Electric Europe BV
Address:Gothaer strase 8, 40880 Ratingen, Germany
4.1 Requirements for Conformance to EMC Directive
The EMC Directive specifies that products placed on the market must "be so con-
structed that they do not cause excessive electromagnetic interference (emis-
sions) and are not unduly affected by electromagnetic interference (immunity)".
The applicable products are requested to meet these requirements.
The sections 4.1.1 through 4.1.3 summarize the precautions on conformance to
the EMC Directive of the machinery constructed using the GOT.
The details of these precautions has been prepared based on the requirements
and the applicable standards control.
However, we will not assure that the overall machinery manufactured according to
these details conforms to the above-mentioned directives.
The method of conformance to the EMC Directive and the judgment on whether or
not the machinery conforms to the EMC Directive must be determined finally by
the manufacturer of the machinery.
4.1.1 Standards applicable to the EMC Directive
The following products have shown compliance through direct testing (to the iden-
tified standards) and design analysis (forming a technical construction file) to the
European Directive for Electromagnetic Compatibility (89/336/EEC) when used as
directed by the appropriate documentation
Type :Programmable Controller (Open Type Equipment)
Models :MELSEC GOT series products, identified here, manufactured from
January 7th, 2008
GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ, GT1155-QSBDA,
GT1150-QLBDQ, GT1150-QLBDA (For this product see note under and
over the page).
4.1.2 Control cabinet
The GOT is an open type device (device installed to another device) and must be
installed in a conductive control panel or cabinet.
It not only assure the safety but also has a large effect to shut down the noise gen-
erated from GOT, on the control panel.
1) Control cabinet
a) Use a conductive control cabinet.
b) When attaching the control cabinet's top plate or base plate, mask paint-
ing and weld so that good surface contact can be made between the
cabinet and plate.
c) To ensure good electrical contact with the control cabinet, mask the
paint on the installation bolts of the inner plate in the control cabinet so
that contact between surfaces can be ensured over the widest possible
area.
d) Earth the control cabinet with a thick wire so that a low impedance con-
nection to ground can be ensured even at high frequencies. (22mm 2
wire or thicker is recommended.)
e) Holes made in the control cabinet must be 10 cm (3.94”) diameter or
less. If the holes are 10cm (3.94”) or larger, radio frequency noise may
be emitted.
In addition, because radio waves leak through a clearance between the
control panel door and the main unit, reduce the clearance as much as
practicable.
The leakage of radio waves can be suppressed by the direct application
of an EMI gasket on the paint surface.
2) Connection of power and ground wires
Ground and power supply wires for the GOT must be connected as described
below.
a) Provide an earthing point near the GOT. Earth the power supply's FG
terminal (FG: Frame Ground) with the thickest and shortest wire possi-
ble. (The wire length must be 30cm (11.18”) or shorter.)
The FG terminal function is to pass the noise generated in the GOT to
the ground, so an impedance that is as low as possible must be
ensured. As the wires are used to relieve the noise, the wire itself carries
a large noise content and thus short wiring means that the wire is pre-
vented from acting as an antenna.
Note) A long conductor will become a more efficient antenna at high fre-
quency.
3) Electrical shock prevention
In order to such as the operators from electric shocks, the control box must have
the following functions :
a) The control cabinet must be equipped with a lock so that only skilled or
qualified personnel.
b) The control cabinet must be fitted with advice which automatically stops
the power supply when the cabinet is opened.
4) Dustproof and waterproof features
The control box also has the dustproof and waterproof functions. Insufficient
dustproof and waterproof features lower the insulation withstand voltage, resulting
in insulation destruction.
The insulation in our GOT is designed to cope with the pollution level 2, so use in
an environment with pollution level 2 or better.
Pollution level 1:An environment where the air is dry and conductive dust does
not exist.
Pollution level 2:An environment where conductive dust does not usually exist,
but occasional
temporary conductivity occurs due to the accumulated dust.
Generally, this is the level for inside the control box equivalent a
control room or on the floor of a typical factory.
Pollution level 3:An environment where conductive dust exits and conductivity
may be generated due to the accumulated dust.
An environment for a typical factory floor.
Pollution level 4:Continuous conductivity may occur due to rain, snow, etc.
An outdoor environment.
4.1.3 Grounding
It is necessary to use the GOT grounding terminal only when it is in the grounded
condition.
Be sure to ground the grounding for the safety reasons and EMC Directives.
Functional grounding : Improves the noise resistance.
Standard Remark
EN61131-2 : 2007
Programmable controllers
- Equipment, requirement and tests
EMI
Compliance with all relevant
aspects of the standard.
(Radiated Emissions)
EMS
Compliance with all relevant
aspects of the standard.
(ESD,RF electromagnetic field,
EFTB, Surge, RF conducted
disturbances and Power
frequency magnetic field)
4.2 Wiring Precautions the Part which Matches the EMC
Directives
Connect and wire GOT equipment as instructed below.
If the GOT equipment is configured in a way that differs from the following
instructions then the system will not comply with EMC directives.
4.2.1 About the cable used
Connect and wire GOT equipment as instructed below.
If the GOT equipment is configured in a way that differs from the following
instructions then the system will not comply with EMC directives.
Bus connection cable
The following products are used in the EMC specification compatibility test con-
ducted by Mitsubishi Electric Corporation.
ZCAT3035-1330 ferrite core manufactured by TDK corporation
AD75CK-type cable clamp manufactured by MITSUBISHI
Zipper tube SHNJ type manufactured by Zippertubing(Japan),Ltd.
EX.1
EX.2
EX.3
GOT
Unit
Existing Cables User Made Cables
GT1155-
QTBDQ,
GT1155-
QSBDQ,
GT1150-
QLBDQ
GT15-QC B,GT15-QC BS modified as
shown in EX.1.
Peel the sheath at both ends of the cable,
and expose the shield braided wire for
grounding. (For grounding with
clamps.(refer to Section 4.2.3.))
The cable need to
be independently
tested by the user
to demonstrate
EMC compatibility
when they are used
with the GOT, the
PLC of MELSEC-Q
series, MELSEC-
QnA series, and
MELSEC-A series.
GT1155-
QTBDA,
GT1155-
QSBDA.
GT1150-
QLBDA
GT15-C BS,cGT15-C EXSS-S1
modified as shown in EX.2.
Peel the sheath at both ends of the cable,
and expose the shield braided wire for
grounding. (For grounding with
clamps.(refer to Section 4.2.3.))
Other bus connection cables modified as
shown in EX.3.
Wind cable shield material around the
cable, and pull out the grounding braided
wire of the cable shield material.
Attach the ferrite core to the cable in the
specified position and insert the braided
wire for grounding into the ferrite core.
Programmable
controller
GOT units
360 (14.17)
or less
360 (14.17)
or less
Unit: mm (inch
)
40
(1.57)
40
(1.57)
Unit: mm (inch
)
60 (2.36)
or less
60 (2.36)
or less
GOT units
Programmable controller
/GOT units
Ferrite Core
(ZCAT3035-1330)
360 (14.17) or less 360 (14.17) or less
40
(1.57)
40
(1.57)
Ground wires
(280 (11.0))
80
(3.15)
GOT unitsFerrite Core
(ZCAT3035-1330)
40 (1.57) or less
80
(3.15)
40 (1.57) or less
Cable shield material
Grounding braided wire
(200 (7.87))
Grounding braided wire
(50 (1.97))
Programmable contoller
Unit: mm (inch)
4.2.2 Method to connect the power wire and ground wire
1) GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ,
GT1155-QSBDA, GT1150-QLBDQ, GT1150-QLBDA
Twist the 24VDC cables to connect to the GT1155-QTBDQ, GT1155-QTBDA,
GT1155-QSBDQ, GT1155-QSBDA, GT1150-QLBDQ, and GT1150-QLBDA.
The ferrite filter is not required for the 24VDC cables.
the GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ, GT1155-QSBDA,
GT1150-QLBDQ, and GT1150-QLBDA unit requires an additional ferrite filter to be
attached to the 24V DC power supply cables. The filter should be attached in a
similar manner as shown in the figure opposite, i.e. the power cables are wrapped
around the filter. However, as with all EMC situations the more correctly applied
precautions the better the systems Electro-magnetic Compatibility. The ferrite
recommended is a TDK ZCAT3035-1330 or similar. The ferrite should be placed as
near to the 24V DC terminals of the the GT1155-QTBDQ, GT1155-QTBDA, GT1155-
QSBDQ, GT1155-QSBDA, GT1150-QLBDQ, and GT1150-QLBDA as possible
(which should be within 75mm of the GOT terminal).
4.2.3 Grounding the cable
Use the bus connection cable to ground the cable and grounding wire to the control
panel where the GOT and base unit are installed.
24V DC
INPUT
+-
Up to
75mm
TDK
Braided shield
Cable clamps
GOT FG terminal
FG wire
a) For GT15-C EXSS-1 and GT15-C BS
Ground the ground wire to the FG terminal of
the GOT power supply section.
For the cable clamp attaching details, refer to
AD75CK-type Cable Clamping Instruction Manual
<IB-68682>.
1) Ground the braided shield portion of the cable to
the control panel with the cable clamp (AD75CK).
Bus connection
cable
b) For other bus connection cables Ground
the braided wire for grounding to the control
panel by tightening a screw.
5. INSTALLATION
5.1 Control Panel Inside Dimensions for Mounting GOT
Mount the GOT onto the control panel while considering the following control panel
inside dimensions.
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to
the GOT. Therefore, consider the connector dimensions and bending radius of the
cable as well for installation.
5.2 Panel Cutting Dimensions
Make holes in the panel according to the dimensions list below.
Also, ensure 10mm spaces in upper and lower parts of the panel for mounting fixtures.
Model Name A B
GT1155-QTBDQ
GT1155-QSBDQ
GT1150-QLBDQ
56 (2.20) 40 (1.57)
GT1155-QTBDA
GT1155-QSBDA
GT1150-QLBDA
38 (1.50) 40 (1.57)
No Name
1) Bus connection cable
2) Personal computer connection cable/bar code reader connection cable
2)
1)
152 (5.99)
120 (4.73)
140 (5.52)
A
B
Unit: mm (inch
)
153
+2
-0
10(0.4") or more
10(0.4") or more
Unit: mm (inch
)
121
+2
-0
(6.03" )
+0.08"
-0
(4.77" )
+0.08"
-0
5.3 Mounting Position
When mounting the GOT, the
clearances shown on the right must
be left from a structure or the other
device.
Secure 50mm (1.97") or more on
the left, right and bottom sides of
the GOT to structures or other
devices.
Secure 80mm (3.15") or more on
the top of the GOT from structures
or other devices to allow good
ventilation.
If devices (such as a contactor)
generating radiated noise or those
generating heat are arranged
around the GOT, secure 100mm
(3.94") or more on the back panel.
When using the CF card, secure a sufficient distance on the left side to allow
installation and removal of the CF card.
[Securing 100mm (3.94") or more is recommended.]
5.4 Control Panel Inside Temperature and Mounting Angle
When mounting the main unit to a control panel or similar, set the display section
as shown below.
When the temperature inside the control panel is 40 to 55 (Horizontal mount),
40 to 50 (Vertical mount), the mounting angle should be in the range 60 to
105 degrees.
The GOT will be
deteriorated earlier if it is
used at the mounting angle
other than the above.
Therefore, the temperature
inside the control panel
should be within 40 .
5.5 Installation Procedure
The GOT is designed to be embedded into a panel. Mount the GOT by following
the procedure below. For panel cutting dimensions, refer to Section 4.2. Note that
the panel thickness should be within 5mm.
1) Inserting into the panel face
Insert the GOT from the front side of
the panel.
2) Fixing the GOT
Engage the hook of the mounting
fitting (accessory) to the unit fixing
hole of the GOT and tighten the
screw until the GOT is fixed with the
mounting bolt (accessory).
The GOT will be fixed in 4 upper/
lower parts.
Tighten the mounting screw with the
specified torque.
(Failure to do so may distort the
panel and make a surface waviness
on the protective sheet.)
3) A protection film is attached on the display section of GOT prior to shipment.
Remove the film when the installation is completed.
50mm
(1.97")
or
more
80mm (3.15") or more
50mm (1.97") or more
*1 To use the CF card, leave sufficient
distances for removal and installation
of the CF card.
50mm
(1.97")
or
more
*1
GOT
back
panel
GOT
display
section
Control
panel,
etc.
105˚
60˚
Mounting hol
e
Mounting
fitting
Mounting
screw
Magnified illustration