7.38
Bimba Position Control System
Application
Example
The following section will review two examples, one example shows a PFC application, and the second example shows
a PTF rotary example.
PFC Example
Let’s say we have just finished the installation procedure for a Bimba PFC Cylinder with 10 inches of stroke, and are
using a 0-10 VDC input command signal. There is a retracted hard stop at 1.5 inches of cylinder stroke and an extended
hard stop at the 9.0 inches of cylinder stroke.
Therefore:
• After adjusting the Span setting, 10 volts is equivalent to 9.0 inches of cylinder rod extension.
• After adjusting the Zero setting, 1.5 inches of cylinder rod extension will equal 0 volts.
Therefore, 0 to 10 volts covers the 7.5 inch (9.0" - 1.5") range of motion.
Using the following formula:
The command signal can be translated into actuator displacement with the following formula:
CS = d * R / t + Z
where:
CS = the command signal required to achieve a desired position
d = the displacement the desired position is from the zero position
R = the full range of the command signal
t = full scale travel of the actuator (Note: for PTF rotary actuators with total rotation less than 180°
always make t = 180)
Z = the command signal for the zero position