11 - 5 11 - 5
MELSEC-Q
11 I/O MODULE TROUBLESHOOTING
Table 11.2 Output Circuit Problems and Corrective Actions (Continued)
Condition Cause Corrective Action
Example 3
The load is
not turned
OFF. (Triac
output)
The load current is lower than the minimum
load current.
Triac
Surge suppresso
r
Phototriac
QY22
Control
circuit
Load
When the load current is lower than the
minimum load current of the output module,
the triac does not operate, causing the load
current to flow into a phototriac as shown
above.
If an inductive load is connected in this state,
the load may not be turned OFF since surge
at the time of OFF is applied to the phototriac.
Connect a resistor to both ends of a load so
that the load current is higher than the
minimum load current.
Load
Resistor