Mitsubishi RS232/485/LAN Serial Communication Control Uživatelský manuál Strana 8

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 11
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 7
IntesisBox
®
Modbus Server - Mitsubishi Electric G50 datasheet v10 r11 eng
TRADEMARKS: All trademarks and tradenames used in this document are acknowledged to be the copyright of their respective holders.
Signals available per every Mitsubishi Electric City Multi AC indoor unit or group
of indoor units
Property
Description / Status
Drive
Start/Stop
Read/Write: ON, OFF
Mode
AC Mode
Read/Write: COOL, DRY, FUN, HEAT, AUTO, HEAT RECOVERY,
LC_AUTO, BYPASS
Read: AUTO HEAT, AUTO COOL
SetTemp
Temperature Set Point (only integer numbers allowed)
Read/Write: For COOL or DRY mode:19..30 ºC, for HEAT mode: 17..28 ºC, for
AUTO mode:19..28 ºC)
AirDirection
Air output direction
Read/Write: HORIZONTAL, MID1, MID2, VERTICAL, SWING
FanSpeed
AC fan speed or LOSSNAY
Read/Write: HIGH, MIDH, MIDL, LOW
RemoCon
Prohibition for General control from the local panel
Read/Write: PROHIBIT, PERMIT
DriveItem
Prohibition for ON/OFF control from the local panel
Read/Write: CHK_ON, CHK_OFF
ModeItem
Prohibition for Mode control from the local panel
Read/Write: CHK_ON, CHK_OFF
SetTempItem
Prohibition for Set Point control from the local panel
Read/Write: CHK_ON, CHK_OFF
FilterItem
Prohibition for Filter Reset control from the local panel
Read/Write: CHK_ON, CHK_OFF
Ventilation
Operational status for LOSSNAY or OA
Read/Write: HIGH, LOW, OFF
FilterSign
Status for Filter Dirty
Read: ON, OFF
Write: RESET
ErrorSign
Error status
Read: ON, OFF
Write: RESET
InletTemp
Ambient Temperature
Read: 0.0 to 99.9
G50 Communication
Error
Communication error with G50
Virtual signal generated by IntesisBox to indicate the status of the
communication with the G50.
Group
Communication Error
Group communication error
Virtual signal generated by IntesisBox to indicate that the group is not
configured into the G50.
Polling Active
Polling active
Virtual signal to indicate or set if the Group is active or not active during the
polling process.
Zobrazit stránku 7
1 2 3 4 5 6 7 8 9 10 11